Description Includes interface to the inverter for fault codes and other data. 5 years of hosting and software license The LGate 330 can be configured to monitor nearly any type of PV system. The standard configuration consists of an industrial gradedatalogger and revenue-grade energy meter mounted inside a weatherized enclosure. DATA COLLECTION The LGate uses the RS-485 Modbus protocol to communicate with downstream devices. Any device that supports Modbus can be connected and monitored by the LGate. Up to 250 devices can be connected through the Modbus loop. CONNECTIVITY Once the LGate collects and stores performance data from connected devices, it will upload batches of data at regular intervals to the Locus Energy Smart Monitoring website. SPECIFICATIONS DATALOGGER * Processor: ARM9 embedded CPU * OS: Linux 2.6 * Memory: 32 MB RAM * Logging interval: 1 to 60 minutes, user selectable(default 5 minutes) COMMUNICATION * LAN: RJ45 10/100 Ethernet, full half,duplex, auto polarity * Cellular (optional): GSM/CDMA * Networking: DHCP or hard static IP POWER METER * Voltage Inputs: 600/347V, 480/277V, 208/120V * Phases: Single phase, Split phase, Three phase at 50 or 60 Hz * Current Inputs: mV full scale output CTs, mA output solid/split core CTs, 5A from standard CTs